A combination of choice of aluminium or copper busbars, standardised quality and unique energy saving features make Ti a truly profitable investment.
The Ti range is the only range of electrification solutions to offer the option of type-tested aluminium or copper busbar configurations, allowing you to make your installation even more cost- effective, without compromising on safety.
In any large building, energy costs often constitute as much as 60% of the total operating cost. The Ti has a unique double-deck Busbar arrangement that reduces impedance and heat loss by reducing detrimental factors like proximity and skin effect, thereby saving almost 40% energy over conventional systems.
The Ti has a compartmentalised design which can be assembled by qualified builders around the world. So, you enjoy the benefits of timely delivery, quick installation and savings – even before you switch the system on.
All doors are provided with concealed hinges to reduce downtime during maintenance. Concealment provides better security against unauthorised access to feeders and makes a post maintenance paint touch-up optional.
A combination of choice of aluminium or copper busbars, standardised quality and unique energy saving features make Ti a truly profitable investment.
Ti is a design verified assembly, in accordance with IEC 61439, assuring you of the highest levels of quality and safety, from design to assembly.Ti is a design verified assembly, in accordance with IEC 61439, assuring you of the highest levels of quality and safety, from design to assembly.
Busbars in the Ti range have higher clearances than those prescribed by global switch-board standards (25 mm – Ph to Ph and 19 mm - Ph to N/Ph to E), offering a superior level of safety.
The Ti's panel doors are designed to prevent accidental opening. We have also placed earthing contacts on every door and an Earthbar running the length of the switchboard, connected to structural members. These ensure that the outer surfaces do not have stray voltages, as this could harm an operator.
The Busbars in the Ti range are equipped with polyester glass supports for insulation. You also have the choice to install heat-shrunk PVC sleeves for extra protection.
A minimum ingress protection of IP2X is provided even with the doors open to ensure that an operator does not come in contact with live terminals or parts during maintenance.
Front access terminations and rotary knobs ensure that an operator does not come in contact with live terminals or parts during maintenance
Standards | IS 8623, IEC 61439 | ||||
---|---|---|---|---|---|
Insulation Characteristics | Clearance | >20 mm | |||
Creepage Distance | >20 mm | ||||
Overvoltage category Pollution degree |
II / III/ IV 3 |
||||
Field condition | Inhomogeneous (non-uniform) | ||||
Electrical Characteristics | Voltage Ratings | Rated operational voltage (Ue) | 415-690 VAC, 24-220 VDC | ||
Rated insulation voltage (Ui) | 690 v | ||||
Rated impulse withstand voltage (Uimp) | 6/8kV | ||||
Rated frequency (fn) | 50 / 60 Hz | ||||
Current Ratings | Main Horizontal busbars: | ||||
Rated current (lnA) | up to 4000 A | ||||
Rated peak withstand current (Ipk) | up to 105 kA | ||||
Rated short-time withstand current (lcw) | up to 50 kA, Is | ||||
Vertical Distribution busbars : | |||||
Rated current (lnA) | 1440A | ||||
Rated peak withstand current (Ipk) | up to 105 kA | ||||
Rated short-time withstand current (lcw) | up to 50 kA, Is | ||||
Mechanical Characteristics | Degree of protection | In accordance with IEC 60529: | |||
External | IP 4X/54* | ||||
Internal | IP 2X | ||||
Forms of seperation | As per 'EC 61439 - 2 | Form III/IV* | |||
Dimensions | Height (mm) | 1800, 2000, 2200, 2400 | |||
Width (mm) | 440, 600, 800, 1000 (ACB section) | ||||
850, 1100, 1400, 1650, 1900 (Outgoing section) | |||||
Depth (mm) | 440, 600, 900, 1000, 1100 (ACB section) 440, 600 (Outgoing section) |
||||
Surface Treatment | Structure | Alu-zinc / powder coated /printed | |||
Internal Components External Components |
Alu-zinc / Powder Coated / Printed Powder Coated / Printed |
||||
Resistance to Corrosion | Damn heat cycling test | IEC 60068-2-30 | |||
Salt mist test | IEC 60068-2-11 | ||||
Plastic Components | Plame Retardant, self-extinguishing, Halogen-free | IEC 60695-2-10, IEC 60695-2-11 |